This guide explains how to test relays, heater limit switches, and electrical current draw when troubleshooting your Genuine Comfort PTAC.
Important: Electrical testing must be performed by a qualified service technician. Always disconnect power and verify the unit is de-energized before testing resistance or continuity.
1. Testing Relays
Relays control the operation of electrical components within the PTAC.
- Identify the relay coil terminals using the applicable wiring diagram.
- Isolate the relay coil from the circuit as required.
- Set the multimeter to resistance (Ω).
- Connect the probes across the coil terminals and record the reading.
Example Relay Specifications:
- Coil voltage: 12 VDC
- Coil resistance: 120 Ω ±10%
- Acceptable resistance: 108–132 Ω
An OL reading may indicate an open coil. Always verify the applicable relay specifications. Normal coil resistance does not confirm that the relay contacts are functioning correctly.
2. Testing Heater Limit Switches
Heater limit switches protect the unit from overheating.
- Low Limit: Interrupts electric heating when the specified temperature is reached.
- High Limit: Provides additional protection against excessive temperatures.
For example, an L130F-30F automatic-reset limit opens at 130°F and nominally resets at 100°F.
How to Test
- Disconnect power and allow the heater to cool.
- Disconnect the wiring from the limit switch.
- Set the multimeter to resistance or continuity mode.
- Place one probe on each terminal.
Closed circuit – Continuity is present.
Open circuit – The limit switch may be tripped or faulty.
Important: Repeated limit switch activation requires further investigation. Never bypass a heater limit switch.
3. Checking Amperage
- Use an appropriately rated AC clamp meter.
- Place the clamp around one individual conductor.
- Record the amperage during the required operating mode.
- Compare the reading with the applicable unit or component specifications.
Warning: Amperage testing on an energized unit must only be performed by a qualified service technician.
Need Assistance?
Contact technical@genuinecomfort.com with your unit's model number, serial number, and multimeter readings.