Temperature sensors help a Genuine Comfort PTAC monitor temperatures and regulate heating and cooling operation.
This guide explains how to test applicable temperature sensors using a multimeter and identify potential sensor failure.
Important: Temperature sensor testing involves accessing internal electrical components. This procedure should be performed by a qualified service technician.
What Is the Purpose of Temperature Sensors?
Temperature sensors provide temperature readings to the unit's main control board.
Depending on the unit's design, temperature sensors may monitor:
- Indoor room temperature.
- Indoor coil temperature.
- Outdoor ambient temperature.
- Outdoor coil temperature.
- Other operating temperatures.
A faulty temperature sensor may affect heating or cooling performance, cause inaccurate temperature readings, or trigger an error code.
Tools and Preparation
Before beginning, have the following available:
- Digital multimeter capable of measuring resistance (kΩ).
- Applicable temperature sensor resistance chart.
- Thermometer to verify the temperature surrounding the sensor.
- Appropriate tools for accessing the sensor connections.
Important Safety Precautions
- Turn off the PTAC unit.
- Disconnect the unit from its electrical power source.
- Verify that the unit is de-energized before accessing internal components.
- Disconnect the temperature sensor from the mainboard before measuring its resistance.
Never measure resistance on an energized circuit.
How to Test a Temperature Sensor
Step 1: Identify the Temperature Sensor
Locate the temperature sensor requiring testing using the applicable wiring diagram or service instructions.
Confirm the sensor type before proceeding, as resistance specifications may differ.
Step 2: Set the Multimeter
Set your digital multimeter to measure resistance in kilo-ohms (kΩ), using an appropriate measurement range.
Step 3: Connect the Multimeter Probes
Place the red and black multimeter probes across the two terminals of the disconnected temperature sensor connector.
Ensure both probes make proper contact with the terminals.
Illustration showing how to measure temperature sensor resistance using a digital multimeter.
Step 4: Check the Resistance Reading
Allow the sensor to stabilize at the surrounding temperature before recording the resistance measurement.
The following reference values apply to the sensor types identified in this guide at 25°C (77°F).
Temperature Sensor Resistance Specifications
| Sensor | Resistance at 25°C (77°F) | Tolerance |
|---|---|---|
| T1 / T2 / T3 / T4 | 5 kΩ | ±2% |
| T5 (Inverter C Series only) | 50 kΩ | ±3% |
Important: These resistance specifications should only be used for applicable sensor types and unit models.
Understanding Your Multimeter Reading
| Multimeter Reading | Possible Condition |
|---|---|
| Within the specified resistance range at the measured temperature | Sensor resistance is within specification |
| Approximately 0 Ω | Possible short-circuited sensor |
| OL or infinite resistance | Possible open-circuited sensor |
| Outside the expected resistance range | Possible faulty sensor or incorrect testing conditions |
Before replacing a sensor, verify the sensor temperature, multimeter settings, probe connections, and applicable resistance specifications.
What If the Temperature Is Not 25°C (77°F)?
Temperature sensor resistance changes with temperature.
If testing at a temperature other than 25°C (77°F), refer to the applicable temperature sensor resistance chart attached to this article.
Compare the measured resistance with the specified resistance value at the corresponding temperature.
Common Signs of a Potential Temperature Sensor Issue
- Possible symptoms include:
- Temperature sensor-related error codes.
- Inaccurate room temperature readings.
- Heating or cooling stopping unexpectedly.
- Difficulty maintaining the desired room temperature.
- Intermittent or abnormal unit operation.
- These symptoms do not necessarily indicate a defective sensor. Wiring connections, control boards, and other components should also be evaluated.
Need Assistance or Replacement Parts?
If you require assistance testing a temperature sensor or identifying the correct replacement, contact Genuine Comfort Support.
Please provide your unit's model number, serial number, error code (if applicable), and measured sensor resistance and temperature.
For technical assistance, email technical@genuinecomfort.com.