This guide explains how to test compressor windings using a multimeter on applicable fixed-speed GC42 and GCDM PTAC units.
Important: This procedure must be performed by a qualified service technician. Disconnect power, verify the unit is de-energized, and safely discharge the capacitor before testing.
1. Identify the Compressor Terminals
Inspect the compressor wiring and terminals for signs of burning or damage.
Identify the three compressor terminals:
- C: Common
- R: Run
- S: Start
Compressor terminal identification – Common, Run and Start.
2. Test Compressor Winding Resistance
- Disconnect the wires from the compressor terminals.
- Set the multimeter to resistance (Ω).
- Measure resistance between C–R, C–S, and R–S.
- Record and compare the readings.
| Terminals | Expected Reading |
|---|---|
| C–R | Lowest resistance |
| C–S | Higher resistance |
| R–S | Approximately the sum of C–R and C–S |
An OL reading may indicate an open winding or an open internal overload protector.
3. Check for a Ground Fault
Measure resistance between each compressor terminal and a clean, bare metal surface on the compressor shell.
- OL: No continuity detected to ground.
- Continuity or low resistance: Possible grounded compressor winding.
Important: Resistance specifications vary by compressor model. This test alone does not confirm that the compressor is fully functional.
Need Assistance?
Contact technical@genuinecomfort.com with your unit's model number, serial number, and resistance readings.